Emergency Lighting Requirements for Healthcare Facilities in Australia

Healthcare facilities (hospitals, aged care, clinics, etc.) have stringent emergency lighting requirements to ensure the safe evacuation of patients, staff, and visitors during emergencies. Compliance with Australian standards is critical for patient safety and regulatory adherence. Below is an overview of the requirements under Australian regulations.

1. Governing Standards & Regulations

Commercial emergency lighting must comply with:

Mandatory in:

A. Illumination Levels

Area
Minimum Lux
Duration

Escape routes

0.2 lux

90 minutes

Exit doors & stairwells

1 lux

90 minutes

Operating theatres & ICUs

Maintained lighting (no drop in illumination)

Generator-backed

B. Exit Signage

Test
Action

6-Monthly

90-minute test as per AS 2293.2

Annually

90-minute test and additional testing as per AS 2293.2

Documentation

Logbook - Required for audits