Clean, calming lighting that supports patient care, staff focus, and clinical accuracy.
Healthcare facilities (hospitals, aged care, clinics, etc.) have stringent emergency lighting requirements to ensure the safe evacuation of patients, staff, and visitors during emergencies. Compliance with Australian standards is critical for patient safety and regulatory adherence. Below is an overview of the requirements under Australian regulations.
Commercial emergency lighting must comply with:
Mandatory in:
|
Area
|
Minimum Lux
|
Duration
|
|---|---|---|
|
Escape routes |
0.2 lux |
90 minutes |
|
Exit doors & stairwells |
1 lux |
90 minutes |
|
Operating theatres & ICUs |
Maintained lighting (no drop in illumination) |
Generator-backed |
|
Test
|
Action
|
|---|---|
|
6-Monthly |
90-minute test as per AS 2293.2 |
|
Annually |
90-minute test and additional testing as per AS 2293.2 |
|
Documentation |
Logbook - Required for audits |
Our designs are known to contain an element of surprise and unconditional perfection. An enigmatic rotation mechanism, an unexpected light beam, a question: how does it work? Discover our product stories and get ready for the extraordinary.